Model A2G-10 Differential Pressure Gauges

Category: .

DOWNLOAD DATASHEET AND CATALOGUE

Applications

  • For dry, clean, non-aggressive gases, usually air
  • Monitoring of blowers and ventilators
  • Filter monitoring via differential pressure
  • Positive overpressure in clean rooms
  • Positive and negative pressure in isolation chambers

Product features

  • Zero adjustment in front
  • Simple mounting and dismounting
  • Two part construction (measuring element and case)
  • Scale ranges from 0.2 InWC (50 Pa) to 50 InWC (12,500 Pa)

Specifications

Design
Per EN 837-3 and HVAC regulations

Nominal size
4½”

Accuracy
± 3.0 % of full span
± 5.0 % of full span, ranges ≤ 0.5 InWC (125 Pa)

Ranges
0 / 0.2 InWC (50 Pa) up to 0 / 50 InWC (12,500 Pa)

Pressure units
InWc (standard)
Other available units: kPa, Pa, mmWC, cmWC, mmHg

Compound ranges
Starting from -0.1 / +0.1 InWC (-25/+25 Pa)
(other pressure units and dual scales are available)

Pressure limitation
Steady: full-scale value
Fluctuating: full-scale value

Overpressure Safety
80 InWC (20 kPa)

Max working pressure (static pressure)
80 InWC (20 kPa)

Temperature limits
Ambient: -22 °F… 176°F (-30oC…+80oC)
Media: 3 °F…122°F  (-16oC…+50oC)

Temperature error
Additional error when temperature changes from reference temperature of 68°F (20°C) +0.5% of span for every 18°F (10°K) rising or falling.

Ingress protection
NEMA 3 (IP 54 per EN 60529 / IEC 529)

Process connection
Plastic
Lower mount (LM) or back mount G 1/8 female for hose connector
Supplied with straight or angled hose barb adaptors 1/8″, 3/16″ (standard). 1/4″ hose barb adaptors available

Separating diaphragm
Silicone rubber

Movement
Frictionless magnetic transmission

Dial
Aluminum, scale over 90 degrees of angle

Pointer
Plastic black

Housing/Mounting case
Black thermoplastic, high impact resistant

Window
Polycarbonate

Add a Review